Series 9660

Lead-free brass backflow preventer with threaded connections

Good to know Data & Facts

Valve size

DN 15 to DN 20
1/2" to 3/4"

Pressure

Inlet pressure: 1.5 bar to 10 bar

Temperature

5 °C to 65 °C
Product design

straightway form

Material

Lead-free brass

Nominal width

DN 15 to DN 20
1/2" to 3/4"

Medium
  • Potable water
Temperature in °C

5 °C to 65 °C

Pressure in bar

Inlet pressure: 1.5 bar to 10 bar

The 9660 backflow preventer is a compact safety device designed to protect drinking water systems in accordance with DIN EN 1717 up to fluid category 4.

As a mini backflow preventer in DN10, it is particularly suitable for applications with limited installation space, such as heating system top-ups, dosing systems or commercial dishwashers.

The operating principle is based on a three-zone pressure system with an inlet non-return valve, a drain valve and an outlet non-return valve (p1 > p2 > p3). This ensures reliable separation between drinking water and non-potable water.

Thanks to lead-free materials, low pressure drop and a compact design, the 9660 meets the highest standards of hygiene, efficiency and integration.

connection types
  • Male thread
  • Water treatment plants
  • Dosing systems
  • Irrigation technology / Cattle fattening
  • Industrial dishwashers
  • Car washes

Safety device for protecting drinking water systems against back-pressure, backflow and back-sucking in accordance with DIN EN 1717, up to and including fluid category 4.

Documents

Do you need the appropriate 3D data for your project?