Series 9660
Good to know Data & Facts
Valve size
DN 15 to DN 201/2" to 3/4"
Pressure
Inlet pressure: 22 psi to 145 psiTemperature
41 °F to 149 °FProduct design
straightway form
Material
Lead-free brass
Nominal width
DN 15 to DN 20
1/2" to 3/4"
Medium
-
Potable water
Temperature in °F
41 °F to 149 °F
Pressure in psi
Inlet pressure: 22 psi to 145 psi
The 9660 backflow preventer is a compact safety device designed to protect drinking water systems in accordance with DIN EN 1717 up to fluid category 4.
As a mini backflow preventer in DN10, it is particularly suitable for applications with limited installation space, such as heating system top-ups, dosing systems or commercial dishwashers.
The operating principle is based on a three-zone pressure system with an inlet non-return valve, a drain valve and an outlet non-return valve (p1 > p2 > p3). This ensures reliable separation between drinking water and non-potable water.
Thanks to lead-free materials, low pressure drop and a compact design, the 9660 meets the highest standards of hygiene, efficiency and integration.
connection types- Male thread
- Water treatment plants
- Dosing systems
- Irrigation technology / Cattle fattening
- Industrial dishwashers
- Car washes
Safety device for protecting drinking water systems against back-pressure, backflow and back-sucking in accordance with DIN EN 1717, up to and including fluid category 4.