Series 651mHNK VA
Good to know Data & Facts
Valve size
DN 151/2"
Pressure
2.5 bar and 3 barTemperature
-10 °C to 120 °CProduct design
angle-type
Material
Stainless steel
Nominal width
DN 15
1/2"
Medium
-
Hot water
Temperature in °C
-10 °C to 120 °C
Pressure in bar
2.5 bar and 3 bar
For the protection of:
- closed circuit water heaters for drinking water and process water
according to TRD 721, DIN 4753 and DIN 1988 for temperatures up to max. 95°C.
The safety valve is installed in the cold water inlet of the hot water heater according to DIN 1988.
connection types- Internal pipe thread
- CHP units (combined heat and power plants)
- closed, thermostatically protected water heating systems with flow temperatures up to 120°C and a permissible heat output up to max. 2,700 kW according to TRD 721, DIN 4751 and DIN EN 12828
In the event of failure of the thermostatic control and limiting devices, the safety valve must blow off the entire heating output of the boiler in the form of hot water and steam. Due to the all-metal design, these safety valves can also be used at high ambient or radiant temperatures.
Safety valves are permanently set and lead-sealed at the factory.
TUV-Germany
Approvals
TÜV.SV.21 516:
Usage
Heating (H)
EU type examination
Approvals
01 202 642B-22 T009 TÜV SV 516:
Usage
Heating (H)
Documents
Do you need the appropriate 3D data for your project?
We will be happy to send you the requested data by e-mail.